Fire resistant cables, copper conductor, mica tape, FR-PVC insulation – 0.6/1KV
- Fire resistant cables, copper conductor, mica tape, FR-PVC insulation – 0.6/1KV
Symbol: FR-CV…mm2 – 0,6/1KV (cs/MICA) 
Hotline
1General
- Used in backup power system in case of fire, suitable for public facilities…, rated voltage 0.6/1KV, fixed wiring.
 
2Applied standard
- TCVN 5935-1 / IEC 60502-1; TCVN 6612 / IEC 60228; IEC 60331 or equivalent standard.
 
3Identification of cores
- By color of insulation: orange.
Or by customer’s requirement.
 
4Structure
- (1) Conductor: By stranded compacted circular copper.
(2) Fire barrier: Mica tape.
(3) Insulation: FR-PVC. 
5Technical characteristics
- Rated voltage U0/U: 6/1 KV.
 - Test voltage: 3,5 kV (5 minutes).
 - Maximum conductor temperature for normal operation is 70°C.
 - Maximum conductor temperature for short-circuit (5s maximum duration) is:
 - 140°C with nominal area larger than 300mm2.
 - 160°C with nominal area up to and include 300mm2.
 - The flame retardant wires have a significant reduced tendency to propagate fire.
 - The wires must self-extinguish after removing the fire source.
 - Test for electric cable under fire condition:
- Flame temperature: 750°C.
 - Flame application time: 90 minutes.
Test voltage: 600V.
 
 